Maintenance
12.2 Changing the type of an I/O module
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
239
Removing I/O modules
To remove an I/O module, follow these steps:
1.
Simultaneously press the top and bottom release buttons of the I/O module.
2.
Pull the I/O module out of the BaseUnit, parallel in a forward direction.
Figure 12-1 Removing I/O modules
See also
Interface modules (
http://support.automation.siemens.com/WW/view/en/55683316/133300
12.2
Changing the type of an I/O module
Introduction
The coding element is a two-part element. When shipped from the factory, both parts are in
the I/O module. When an I/O module is installed for the first time, a part of the coding
element clicks into the BaseUnit. This mechanically prevents the insertion of a different
module type.
There are two versions of the ET 200SP distributed I/O system:
●
Mechanical coding element: Ensures the mechanical coding described above.
●
Electronic coding element: In addition to the above-mentioned mechanical coding, this
version also has an electronic, rewritable memory for module-specific configuration data
(such as the F-destination address for fail-safe modules, parameter data for IO link
master).