Configuration control (option handling)
9.2 Creating the control data record
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
181
Simplified control data record (V1)
For the configuration control of interface modules of the ET 200SP distributed I/O system,
you define a control data record 196 V1.0, which includes a slot assignment. The maximum
slot of the configuration corresponds to the slot of the server module or ET 200AL I/O
module (in a mixed ET 200SP / ET 200AL configuration).
The table below shows the structure of a control data record with explanations of the
individual elements.
Table 9- 4
Structure of the simplified control data record V1.0
Byte
Element
Code
Explanation
0
Block length
4 + maximum slot
Header
1
Block ID
196
2
Version
1
3
Version
0
4
Slot 1 of the station master Slot assignment in the
station option
Control element ET 200SP
Contains the information on which
ET 200SP module is inserted in which
slot.
The value that you need to enter in the
corresponding byte depends on the fol-
lowing rule:
•
If the module exists in the station
option, enter the slot number of the
module.
•
If the module exists as empty slot
(with BU cover), enter the slot number
of the 128. (Example: mod-
ule as empty slot on slot 3: Enter 131
in the control element)
•
If the module does not exist in the
station option, enter 0.
5
Slot 2 of the station master Slot assignment in the
station option
:
:
:
4 + (slot server
module - 1)
Server module slot
Server module slot as-
signment in the station
option*
:
:
:
:
4 + (first slot ET
200AL - 1)
First slot ET 200AL
Slot assignment in the
station option
Control element ET 200AL
Contains information on which ET 200AL
module is inserted in which slot.
The value that you need to enter in the
corresponding byte depends on the fol-
lowing rule:
•
If the module exists in the station
option, enter the slot number of the
module.
•
If the module does not exist in the
station option, enter 0.
:
:
:
4 + (last slot ET
200AL - 1)
Last slot ET 200AL
Slot assignment in the
station option
* The server module must be present in the station option and must not be marked as empty slot (BU cover).
Summary of Contents for Simantic ET200SP
Page 1: ......