Wiring
5.12 Connecting interfaces for communication
Distributed I/O system
110
System Manual, 12/2016, A5E03576849-AG
BA 2×SCRJ BusAdapter mounted
①
Interface module
②
BA 2×SCRJ BusAdapter
③
PROFINET connecting cable (fiber-optic cable)
Figure 5-19 Connecting the BA 2×SCRJ BusAdapter to the interface module
Reusing fiber-optic cable
Note
If you are reusing fiber-optic cables, you must shorten both fiber-optic cores by the amount
of the curved lengths and reassemble the connectors. This will prevent any attenuation
losses caused by re-bent, heavily stressed portions of the fiber-optic cores.
Reference
For more information on the installation guidelines for fiber-optic cables, refer to the
SIMATIC NET PROFIBUS Network Manual