Technical specifications
14.5 Mechanical and climatic environmental conditions
Distributed I/O system
280
System Manual, 12/2016, A5E03576849-AG
Mechanical environmental conditions
The following table shows the mechanical environmental conditions in the form of sinusoidal
vibrations.
Table 14- 9 Mechanical environmental conditions
Frequency band
ET 200SP with
BusAdapters BA 2×FC,
BA 2xSCRJ, BA
SCRJ/FC, BA 2xLC and
BA LC/FC
ET 200SP with
BusAdapters BA 2×RJ45,
BA SCRJ/RJ45 and BA
LC/RJ45
ET 200SP with
IM 155-6 PN BA
ET 200SP with digital
output module F-RQ
1x24VDC/24..230VAC/5
A
5
≤
f
≤
8.4 Hz
3.5 mm amplitude
8.4
≤
f
≤
150 Hz
1 g constant acceleration
10
≤
f
≤
60 Hz
0.35 mm amplitude
---
---
---
60
≤
f
≤
1000 Hz
5 g constant acceleration
Tests of mechanical environmental conditions
The following table provides important information with respect to the type and scope of the
tests of environmental mechanical conditions.
Table 14- 10 Tests of mechanical environmental conditions
Condition tested
Test standard
Comment
Vibrations
2)
Vibration test accord-
ing to IEC 60068-2-6
(sinusoidal)
Type of vibration: Frequency sweeps with a rate of change of 1 oc-
tave/minute.
BA 2×RJ45, BA SCRJ/RJ45, BA LC/RJ45, IM 155-6 PN BA, digital output
module F-RQ 1x24VDC/24..230VAC/5A
•
5 Hz
≤
f
≤
8.4 Hz, 3.5 mm constant amplitude
•
8.4 Hz
≤
f
≤
150 Hz, 1 g constant acceleration
BA 2×FC, BA 2xSCRJ, BA SCRJ/FC, BA 2xLC, BA LC/FC
•
10 Hz
≤
f
≤
60 Hz, 0.35 mm constant amplitude
•
60 Hz
≤
f
≤
1000 Hz, 5 g constant acceleration
Duration of vibration: 10 frequency sweeps per axis at each of three verti-
cally aligned axes
Shock
2)
Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: Half-sine
Shock intensity: 150 m/s
2
peak value, 11 ms duration
Direction of shock: 3 shocks in each direction (+/-) at each of three verti-
cally aligned axes
Repetitive shock
1) 2)
Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: Half-sine
Shock intensity: 25 g peak value, 6 ms duration
Direction of shock: 1000 shocks in each direction (+/-) at each of three
vertically aligned axes
1)
Not applicable in the case of the digital output module F-RQ 1x24VDC/24..230VAC/5A
2)
Not applicable for motor starters