Engineering
Detector line
9
A6V10421795_en--_k
91 | 151
9.4.3 Maintenance
9.4.3.1 Deleting a device
Device deletion is not supported on the panel. It can only be done in the online
configuration tool. See document
for detailed information on how to
delete a device.
9.4.3.2 Accepting replaced/exchanged devices
After replacing faulty devices with new ones or exchanging device locations within
the same
detector line, perform the command of ‘Accept replaced devices’ to
acknowledge device replacement or location exchange. The newly replaced or
exchanged devices inherit all features and parameter settings from the old devices.
Before accepting newly replaced or exchanged devices, note the following:
● Ensure newly replaced devices are of the same type with devices to be
replaced.
● Ensure newly exchanged devices are of the same type and within the same
detector line with devices to be exchanged.
● Power off the detector line before uninstalling and replacing faulty devices.
● Ensure no devices are left out when exchanging device locations.
● Do not change the topology when replacing or exchanging devices.
To accept replaced/exchanged devices
The detector line is powered off. See '
1.
Press
on the keypad.
The 'Main menu' window is open.
2.
Select 'Engineering' and press .
The 'Engineering' window is open.
3.
Select 'Detector line' and press .
The 'Detector line' window is open.
4.
Select 'Maintenance' and press .
The 'Maintenance' window is open.
5.
Select 'Accept replaced devices' and press .
A list of all lines is displayed.
6.
Select a line and press .
A confirmation dialog window is open.
7.
Press
to confirm.
The replaced/exchanged devices are accepted.