Commissioning
Factory reset
10
A6V10421795_en--_k
119 | 151
4.
Enter 'fc360.siemens.com' in the address bar and press <enter>.
'FC360 Panel Configurator' is open.
5.
Click 'Administration'.
6.
In the 'Test report' field, click 'Upload to PC'.
7.
If prompted, enter a path and a file name and click 'OK'.
The test report is stored to the PC.
8.
Log out of 'FC360 Panel Configurator' and disconnect the PC from the panel.
10.12 Factory reset
If a wrong country or language setting was selected during the start-up of the
panel, execute a factory reset to restart.
See chapter '
Restoring factory settings [➙ 106]
10.13 Adding output card (4M)
Output card (4M) is installed correctly. See chapter '
1.
Connect the PC to the panel.
2.
Open a web browser.
3.
Enter 'fc360.siemens.com' in the address bar and press <enter>.
'FC360 Panel Configurator' is open.
4.
Enter access level 3 password to log into access level 3 on the panel.
5.
Configure output card (4M). See document
chapter '
6.
Check output card (4M) function.
7.
Log out of 'FC360 Panel Configurator' and disconnect the PC from the panel.