Appendix C: Door holder function
17
A6V10421795_en--_k
135 | 151
– 'Disable(D)'. Disable events detected by the corresponding caused devices
or zones.
– 'F&T'. Fire or trouble events detected by the corresponding caused devices
or zones.
– 'F&D'. Fire or disable events detected by the corresponding caused devices
or zones.
– 'T&D'. Trouble or disable events detected by the corresponding caused
devices or zones.
– 'F&T&D'. Fire, disable or trouble events detected by the corresponding
caused devices or zones.
Once a configured logic control is triggered, fire door releasers or door holders
are activated accordingly.
Door holder off function
Use this function to disable the 'Door holder' function when an input is closed. All
programmed fire door releasers or fire electromagnetic door holders are
deactivated, even though some of them were already activated by configured logic
controls.
Input modules, I/O modules or digital inputs on the mainboard IO can be used to
turn off the 'Door holder' function if the input usage type is configured as 'Door
holder off' in FC360 Panel Configurator.
To configure an input as 'Door holder off' in FC360 Panel
Configurator
If configuring an input module or input channel of an I/O module, ensure the
configured module/channel is assigned to device type 'Technical Dev.' in task
card 'Detection & Control'.
1.
In task card 'Detection & Control', click an input module or an input channel of
an I/O module, or click an onboard input under 'Onboard IO'.
2.
In the pane of 'Element Properties', select 'Door holder off' from the usage
drop-down list.