Appendix E: Device type list
19
A6V10421795_en--_k
139 | 151
Device types
Parameters
Values
Optional
zone
Optional devices
Control Dev.
1
-
-
-
General output on the FDCIO221,
FDCIO222, FDCIO224, FDCIO361
Door holder
1
-
-
-
General output on the FDCIO221,
FDCIO222, FDCIO224, FDCIO361
EVAC siren Dev.
2
-
-
-
Addressable alarm devices (without voice
indication) and sounder bases on the
detector line: FDS224-R, FDS224-W,
FDS226-RW, FDS226-WW, FDS226-RR,
FDS226-WR, FDSB226-WW, FDSB226-
WR, FDS364, FDS366, DBS720,
FDS221, FDS229, DBS721, DBS728,
DBS729.
EVAC voice Dev.
2
Addressable alarm devices (with voice
indication) and sounder bases on the
detector line: FDS225-R, FDS225-W
FDS227-RW, FDS227-WW, FDS227-RR,
FDS227-WR, FDS227-RW-C, FDS227-
WW-C, FDS227-RR-C, FDS227-WR-C,
FDSB227-WW, FDSB227-WR, FDSB227-
WW-C, FDSB227-WR-C.
1
Devices can only be numbered from 1 to 32. Besides, 'Control' and 'Door holder' devices cannot share the
same device number.
2
Devices can only be numbered from 1 to 64. Besides, 'EVAC siren' and 'EVAC voice' devices cannot share
the same device number.
The FDCI723 CANNOT report a 'Glass broken' event even if it is assigned to
'Manual alarm'.