Installation
C-NET detector line
6
34 | 151
A6V10421795_en--_k
Connection factor
The max. number of connectable C-NET peripherals (126 devices per loop) and
the max. line length (3300 m) depend on the device connection factor. Calculation
must be performed first using 'FC360 Cerberus FIT Quantities tool'
(document ID: A6V10885143).
FC360 series don't support silent verification of the expected loop alarm current
and voltage drop margin of an installation. Use 'FC360 Cerberus FIT Quantities
tool' to calculate the load of the C-NET detector line(s).
6.6.1 Connectable C-NET devices
C NET devices which can be connected to the C-NET
detector line(s). It also highlights the devices with an
external alarm indicator (EAI) or a sounder base (DBS720) that can be
connected to the devices.
X
possible/available
–
not possible/not available
Device type
Type
Description
AI
EAI
DBS720
Point detectors
OP720
Smoke detector
X
X
X
HI720
Heat detector (ROR)
X
X
X
HI722
Heat detector (static) with temperature report
support
X
X
X
OH720
Multi-sensor smoke detector
X
X
X
OOH740
Multi-sensor smoke detector;
DualProtocol Collective
X
X
X
OP360
Smoke detector
X
X
X
HI360
Heat detector (ROR)
X
X
X
OH360
Multi-sensor smoke detector
X
X
X
Special detectors FDF241-9
Infrared flame detector (2 sensors/1 photo diode);
DualProtocol Collective
X
X
–
FDL241-9
Linear smoke detector; DualProtocol Collective
X
X
–
OOHC740
Neural fire and CO detector with ambient
supervision
X
X
X
Manual call
points
FDM221
FDM231
Manual call point, direct action
X
–
–
FDM223
Manual call point, indirect action
X
X
–
FDM224
Manual call point, direct action
X
X
–
FDM225
Manual call point, direct action
X
–
–
FDM226
Manual call point, direct action
X
–
–
FDM365-RP
Manual call point, direct action
X
–
–
Line modules
FDCI221
Input module (1 input)
X
–
–
FDCI222
Input module (4 inputs)
X
–
–
FDCI723
Zone module, ext. powered (1 collective line)
X
–
–
FDCIO221
Input/output module (1 input and 1 output)
X
–
–
Summary of Contents for FC361 Series
Page 6: ......