Entry in the calibration
report
Possible content*
Description
3. Power consumption of
the lines while idling
Loop 1 I(mA) 1.00
The entry shows the measured power
consumption of the line in an unloaded
state.
4. Line resistance - Plus
Loop 2 R+(Ohm) 0.00
The entry shows the measured line
resistance on the line's plus cable in
ohm [Ω].
5. Line resistance - Minus
Loop 2 R-(Ohm) 0.00
The entry shows the measured line
resistance on the line's minus cable in
ohm [Ω].
6. Tolerance of the line
resistance
Loop 1 DRmax(Ohm) 350.00
The entry shows the calculated value
for the maximum tolerance of the line
when faced with a gradual line break
and thermal drift.
* The specified lines, devices, and values are only examples.
9.4.8.3 Troubleshooting
Troubleshooting during line calibration
The following table lists options for troubleshooting for possible fault entries in the
calibration report or on the LCD:
Entry in the calibration
report
Content*
Troubleshooting
1. Calibration status
Loop 1 state false
The last calibration of the lines failed.
Check the other entries in the
calibration report for the lines in order to
narrow down the cause.
Need calibrate (displayed on the LCD)
The line must be recalibrated. The data
from the last calibration is no longer
valid as the line topology and/or
configuration parameters have been
changed in a way that affects the power
consumption of the line.
Recalibrate the line. You will find more
information on this in chapter '