Function overview
Access levels
7
A6V10421795_en--_k
59 | 151
7 Function overview
7.1 Access levels
The panel is protected against unauthorized operation by access levels.
The authorization passwords for access level 2, access level 3 and access
level 3.1 can be changed either directly on panel or with 'FC360 Panel
Configurator'.
Acces
s level
Personnel
Password
(Default)
Function
1
Anybody
No
● View pending events.
2
Authorized user 1234 or
key switch
or input
Operate the system, e.g.
● Acknowledge, operate and reset
events.
● Disable/enable ↑ zone, device, alarm
devices,
↑ RT alarm, and RT fault.
● Perform detection test, lamp test
1
and
voice test
● View event log and compensation
value log.
● Automatic logout after a period of no
operation.
● Access code is not necessary if a key
switch is used.
● Access code is not necessary if the
input configured as ‘access level 2’ is
activated.
3
Commissioning
engineer
9999
● Configure system.
● Automatic logout after a period of no
operation.
3.1
9999
● Restart a ↑ detector line.
4
66666666
● Reset alarm counter.
1
This function is available directly under Main menu for access level 1 if
checkbox 'Lamp test activation possible at access level 1' is checked under
task card 'Other settings' in 'FC360 Panel Configurator'.