Engineering
Detector line
9
A6V10421795_en--_k
97 | 151
9.4.5.3 Viewing type A dependencies
The 'View typeA dependency' function is used to view all devices which have
type A dependency activated.
1.
Press
on the keypad.
The 'Main menu' window is open.
2.
Select 'Engineering' and press .
The 'Engineering' window is open.
3.
Select 'Detector line' and press .
The 'Detector line' window is open.
4.
Select 'View' and press .
The 'View' window is open.
5.
Select 'View typeA dependency' and press .
A list of all devices with activated type A dependencies is displayed.
6.
Select one device and press .
The details of the type A device are displayed as follows.
View typeA dependency L3
Auto alarm 5
Type A inhibit time(sec) 30
The 'Type A function' can be configured by 'FC360 Panel Configurator'.
9.4.6 Locating devices
9.4.6.1 Locating all devices in a zone
Use this function to locate all the devices in a zone.
1.
Press
on the keypad.
The 'Main menu' window is open.
2.
Select 'Engineering' and press .
The 'Engineering' window is open.
3.
Select 'Detector line' and press .
The 'Detector line' window is open.
4.
Select 'Locate' and press .
The 'Locate' window is open.
5.
Select 'Zones' and press .
A list of all zones is displayed.
6.
Select one zone and press .
Two commands are listed: 'Locate' and 'Quit locate'.