15 Appendix A: Alarm Verification Concept
(AVC)
'Alarm Verification Concept' serves the purpose of delayed alarm
transmission and takes into account the interaction of the operating personnel in
the alarming sequence.
Operating personnel are able to examine the indicated fire location in the event of
a fire alarm. Intervention by the fire brigade can be avoided in the event of a false
alarm or minor incident.
Fig. 27: Alarm verification
1
Alarm event
q
Acknowledge at panel
2
Alarming
qx
Not acknowledged
3
Manual call point or
<Alarm delay off> on
panel
T2..
Time T2 to investigate the source of alarm and the fire
location
mx
'Unmanned operation'
operation mode
..T2
X
Time T2 has expired
m
'Manned operation'
operation mode
r
Reset on panel
T1.. Time T1 for attendance
check
rx
Not reset
..T1
X
Time T1 has expired
GA
Alarming (Global alarm)
T2..
T1..
?
..T2 X
..T1 X
1
mx
m
2
q
r
qx
rx
GA
3