Maintenance
Calibrating lines
11
A6V10421795_en--_k
123 | 151
11.5 Calibrating lines
WARNING
Impermissible line configuration
An impermissible line configuration can cause the alarm devices connected to this
line to be supplied with insufficient power in the event of a fire. This prevents the
alarm from sounding in the corresponding parts of a building. This can cause
serious injuries or death.
● Make sure that
all
lines
of a line card have a permissible line configuration by
calibrating
them
successfully
.
Calibrate all lines manually on the
● The line topology has been changed.
● The configuration of the brightness level and/or the sound level of the alarm
devices has changed.
● The PMI displays a calibration error for a line.
The duration of a line calibration consists of a 45-second base time plus about 1
second per installed 'Voice alarm sounder beacon/Voice al. sound. beacon base'
device on the line to be calibrated. This means a line with 252 'Voice alarm
sounder beacon/Voice al. sound. beacon base' devices can be calibrated in about
5 minutes.
You will find more information on line calibration in chapter '
11.6 Completion of work
1. Activate a test alarm through the system operator with
2. Change all 'OFF' status to 'ON'.
3. Have the system owner confirm the revision.