Operation
Operations under access level 2
8
76 | 151
A6V10421795_en--_k
3. Select 'Isolation' and press
.The 'Isolation' window is open.
Isolation L2
1 - Detection
2 - Sounders
3 - RT outputs
4 - Fire control
5 - Control dev.
6 - Door holder device
4. Select 'Detection' and press
. The 'Detection' window is open.
Isolation- Detection L2
1 - Zone
2 - Device
5. Select 'Zone' and press
. A list of all zones is displayed.
Detection - Zone L2
01 Zone 1 (ON)
02 Zone 2 (ON)
T1 Zone T1 (ON)
6. Select the desired zone and press
. A confirmation dialog window is open.
Do you want to disable device?
Yes (OK) or No (C)
7. Press
to confirm. The selected zone is disabled and the 'Isolation' LED is on.
Refer to steps 1~6 to enable a zone.