Installation
Terminals and switches
6
A6V10421795_en--_k
45 | 151
X22 Pin assignment
Pin
Description
1
Message input from the power supply: Battery fault
2
Message input from the power supply: Mains fault
3
Supply input from the power supply (+)
4
Supply input from the power supply (+)
5
Supply input from the power supply (-)
6
Supply input from the power supply (-)
S1: Reset key for panel
Operation
Function
Press one time
Panel shuts down and restarts.
S2: Reset key for detection module (for factory use only)
Operation
Function
Press one time
The C-NET detector lines are powered off and the panel
reports a fatal fault of detection module. You can power
on the C-NET detector lines and remove the fatal fault by
'Reset detection module' function. See '
NOTICE! Do not use! For factory use only! Otherwise
a fatal error will occur!
S3: Switch for buzzer
Position
Function
On
Buzzer enabled (default).
Off
Buzzer disabled.
Note:
Only disable the buzzer for commissioning
purpose. Otherwise, keep it enabled to comply with
EN 54-2.
S4: Switch for earth fault detection
Position
Function
On
Earth fault monitoring activated (default).
Off
Earth fault monitoring deactivated.
Note:
Only deactivate the earth fault detection for
commissioning purpose. Otherwise, keep it activated to
comply with EN 54-2.