Installation
Accessories
6
48 | 151
A6V10421795_en--_k
The LED and button 'Silence/Resound'
on panel PMI are deactivated if the
evacuation module (NL) is installed and configured.
6.11.3 LED indicator (32 zones) (FTO3603-Z1)
Fig. 18: Installation of LED indicator (32 zones)
Function
:
The LED indicator (32 zones) shows the actual alarm status of each zone
(max. 32 zones of a panel).
● Flashing LED indicates the first zone in alarm.
● Static LED on indicates other zones in alarm.
Installation
:
Detailed information on installation is available in document A6V11777319. See
chapter '
Configuration
:
No configuration is required.
NOTICE
● Before installing the LED indicator (32 zones) on an old panel (FC361-xx),
ensure that you’ve updated the panel software to the latest version. The first
16 LEDs function the same as the replaced LED indicator (16 zones).
● You can also install the LED indicator (32 zones) on FC361-YZ or FC361-YA
if the originally-equipped LED indicator (16 zones) needs to be replaced.
● If you have an LED indicator (16 zones) at hand, you can install it on any
panel, but don't assign a device to a zone number larger than 16. Otherwise,
the panel displays no alarm status if the device is activated.
FTO3602-Z1