Appendix C: Door holder function
17
134 | 151
A6V10421795_en--_k
17 Appendix C: Door holder function
Use the 'Door holder' function to control fire door releasers or fire electromagnetic
door holders via output channels of FDCIO221, FDCIO222, FDCIO224 and
FDCIO361.
Once door releasers or door holders are connected to the output channels above
via physical wiring and logic controls are configured in FC360 Panel Configurator,
conditions like fire alarms can trigger the release of fire door releasers or door
holders and then fire doors are activated in case of emergencies. When conditions
like fire alarms are gone, fire doors are deactivated again.
If fire doors are normally open to facilitate people movement but closed under
special conditions like fire alarms, fire door activation means closing of the doors
while fire door deactivation means keeping the doors open.
To configure logic controls for fire door releasers or door
holders in FC360 Panel Configurator
Output channels connecting to fire door releasers or door holders are assigned
to device type 'Door holder' in task card 'Detection & Control'.
Device numbers of these output channels are changed based on specific
layout plans in task card 'Detection & Control'. Note that a device number
cannot be greater than 32 or the same with that of an output channel of
'Control' type.
1.
Expand 'Control devices' and find the door holders to be configured in task card
'Cause & Effect'.
2.
In the 'Panel' section, activate logic controls between the door holders and the
following panel-reported states based on specific layout plans.
– 'Any fire': Any fire event reported in the panel.
– 'Global alarm': Any global alarm event reported in the panel.
– 'Any automatic device': Any device of 'Auto alarm' type is activated and
then a corresponding event is reported in the panel.
– 'Any manual device': Any device of 'Manual alarm' type is activated and
then a corresponding event is reported in the panel.
– 'Any sprinkler device': Any device of 'Sprinkler' type is activated and then a
corresponding event is reported in the panel.
– 'Any 2 auto. devices': Any two devices of 'Auto alarm' type are activated
and then corresponding events are reported in the panel.
– 'Any 2 fire devices': Any two fire detection devices are activated and then
corresponding events are reported in the panel.
– 'Any fault': Any fault event reported in the panel.
– 'Any disable': Any disable event reported in the panel.
– 'AC power fault': Any mains voltage failure event reported in the panel.
– 'Timed channel': Timed channel is activated and then a corresponding
event is reported in the panel. See document
information about 'Timed channel'.
3.
In the 'Zones' section, select one of the following options in the drop-down lists
to configure logic controls between the door holders and zones having 'Auto
alarm' or 'Manual alarm' devices. Expand the zones and do the same to
configure the logic controls between the door holders and individual 'Auto
alarm' or 'Manual alarm' devices.
– 'Fire(F)'. Fire events detected by the corresponding caused devices or
zones.
– 'Trouble(T)'. Trouble events detected by the corresponding caused devices
or zones.