Appendix G: Default settings for panel/devices
21
144 | 151
A6V10421795_en--_k
Manual call points parameters
Devices Attach
AI
Activation of external AI
FDM221 -
-
FDM223 Yes
By the element
FDM224 Yes
By the element
FDM225 -
-
FDM226 -
-
FDM231 -
-
FDM365 -
-
The default setting of AVC function is OFF for all the above devices.
Input parameters of input modules and I/O modules
Devices
Short circuit monitoring
enabled
Inversion
FDCI221
Yes
Normal
FDCI222
Yes
Normal
FDCI361
Yes
-
FDCIO221
Yes
Normal
FDCIO222
Yes
Normal
FDCIO224
Yes
Normal
FDCIO361
Yes
-
The default settings of the following parameters for the above devices are the
same:
● Not in use: No
● Usage: Standard
● Technical device with panel buzzer activation : No
FDCI723 zone module parameters
Items
Default settings
Response time setting
Alarm: 0s / Malfunction: 10s
Line type
Voltage limiting alarm load
EOL type
20V transzorb diode
Device Type
Auto alarm
Not in use
No
AVC function
ON
Latched
Yes