Appendix G: Default settings for panel/devices
21
142 | 151
A6V10421795_en--_k
Outputs on Output card (4M)
Items
Output usage Monitor
creeping open
/ short
Tone
Activation
condition
(cause)
Configurable OUT1 RT Fire
No
-
Global alarm
Configurable OUT2 RT Fault
No
-
Any fault
Configurable OUT3 Sounder line
No
Continuous Any fire
Configurable OUT4 Sounder line
No
Continuous Any fire
Communication interface
Items
Address Trouble
inhibite
d
Baud rate Parity Data
bits
Stop
bits
Flow
control
ESPA
1
No
9600
None
8
1
None
DMS
4
No
9600
None
8
1
None
Ext. printer -
-
9600
None
8
1
None
Special panel settings
Items
Default settings
MCP broken glass message
1
Yes
MCP cannot be disabled
No
Sounder outputs activation via silence/resound
button
No
Resound sounders on new alarm
Yes
Lamp test activation possible at access level 1
Yes
Acknowledge used as silence
No
Acknowledge availability at access level 1
No
Block ackn./reset if RT is active
No
RT Fire Relay, default activated (inverse driven)
OFF
RT Fire LED activated by
RT Fire
RT fault, default activated (inverse driven)
ON
Technical device with panel buzzer activation
No
Technical Latched device with panel buzzer
activation
Yes
Synchronization between EVAC zones (max 3
devices per zone)
No
Internal AI operation in idle mode
Normal: Off
Ext. Alarm Indicator global setting (connected)
Yes
Main power fault delay function
ON
Main power delay time
10 mins
Time for delay alarm (Second)
60 s
Confirm for delay alarm (Second)
60 s