System Manual V2 – MOVITRAC® B
93
5
Explanation of the parameters
Parameters
113
AI1 voltage offset
(up to firmware 12)
Setting range: –10 V ...
0
... +10 V
The zero passage of the setpoint characteristic curve can be moved along
the U
E
axis.
116
AI1 characteristic curve x1
Setting range:
0
... 100 %
117
AI1 characteristic curve y1
Setting range: –100 % ...
0
... +100 %
118
AI1 characteristic curve x2
Setting range: 0 ...
100
%
119
AI1 characteristic curve y2
Setting range: –100 ... 0 ...
+100
%
A 2-point characteristic curve is described by the coordinates x1/y1 and x2/y2, with which the AI1 analog input is
evaluated.
No.
FBG
Name
Description
10V
0V
1V
2V
3V
4V
5V
6V
7V
8V
9V
n
P302/P312
max
-n
P302/P312
max
n
U
E
Reference point
with positive offset
Reference point
with negative offset
(P113)
U offset
Normalized setpoint
+100 %
+100 %
10 V
20 mA
Input
value
Factory setting
Example
0 %
0 V
0 mA
4 mA
P
i
f
kVA
Hz
n
Summary of Contents for MOVITRAC MC07B0037-2A3-4-00