System Manual V2 – MOVITRAC® B
81
4
Fieldbus connection
Technical Data
4.25.7 Fieldbus interface DFS11B for PROFIBUS / PROFIsafe
®
Description
The MOVITRAC
®
B frequency inverter enables you to use the DFS11B option to
connect to higher-level automation systems via PROFIBUS with PROFIsafe
®
thanks to
its powerful, universal fieldbus interface.
Refer to the publication "DFS11B PROFIBUS DP-V1 with PROFIsafe
®
Fieldbus
Interface" for installation.
Electronics data
DFS11B option
External voltage
supply via X26
U = DC 24 V (–15 %, +20 %)
I
max
= DC 200 mA
P
max
= 3.4 W
PROFIBUS
protocol options
PROFIBUS DP and DP-V1 acc. to IEC 61158
Automatic baud
rate detection
9.6 kBaud ... 12 MBaud
Connection
technology
•
Via 9-pin sub D connector
•
Pin assignment acc. to IEC 61158
Bus termination
Not integrated, must be implemented using suitable PROFI-
BUS connector with switchable terminating resistors.
Station address
1 ... 125, adjustable via DIP switches
F address
1 ... 1022, adjustable via DIP switches
Name of the GSD
file
SEW_6009.GSD
DP ident number
6009
hex
= 24585
dec
Application-
specific parame-
ter-setting data
(Set-Prm-User-
Data)
•
Length: 3 bytes
•
Hex parameter setting 00,00,00
DP configura-
tions for
DDLM_Chk_Cfg
See publication "DFS11B PROFIBUS DP-V1 with
PROFIsafe
®
Fieldbus Interface".
Diagnostics data
•
Standard diagnostics: 6 bytes
NOTE
Safety-oriented applications are implemented using PROFIsafe
®
interfaces.
Refer to the publication "DFS11B PROFIBUS DP-V1 with PROFIsafe
®
Fieldbus Inter-
face" for installation.