System Manual V2 – MOVITRAC® B
177
8
TF thermistor and TH bimetallic switch
Installation
8.8
TF thermistor and TH bimetallic switch
The winding temperature is monitored using TF thermistors or TH bimetallic switches.
The connection is made at the TF output VOTF and the TF input DI05TF of
MOVITRAC
®
. The binary input DI05TF must be set to TF signal. The temperature will
then be monitored by MOVITRAC
®
; no additional monitoring unit is required.
A connection can also be made to 24VIO and a binary output when using TH bimetallic
switches. Set the binary input to /External fault.
8.9
Connecting braking resistors BW.. / BW..-T / BW..-P to X3 / X2
A terminal must be set to "/Controller inhibit". K11 must be opened and "/Controller
inhibit" must receive a "0" signal in the following cases:
•
BW...-...-P: The auxiliary contact trips
•
BW...-...-T: The internal temperature switch trips
•
BW...: The external bimetallic relay F16 trips
The resistor circuit must not be interrupted.
Overload protection for braking resistors BW:
Overload protection
Braking resistor type
Design
specified
Internal temperature
switch (..T)
External bimetallic
relay (F16)
BW...
–
–
Required
BW...-...-T
1)
1) Permitted installation: On horizontal or vertical surfaces with brackets at the bottom and
perforated sheets at top and bottom.
Not permitted:
On vertical surfaces with brackets at the top,
right or left.
–
One of the two options (internal temperature switch /
external bimetallic relay) is required.
BW...-003 / BW...-005
Adequate
–
Permitted
T2
T
1
BW...-...-T
RB2
RB1
X2/X3:
+R -R PE
8
9
BW...
F16
X2/X3:
+R -R PE
8
9
4
6
X2/X3:
+R -R PE
BW...-...-P
→
K11
97
95
98
96
F16
→
K11
→
K11