System Manual V2 – MOVITRAC® B
201
9
Startup with DBG60B
Startup
9.9.5
Setting parameters
Proceed in the following order to set the parameters:
•
Use the context key to call up the context menu. In the context menu, select the
"PARAMETER MODE" menu item. Press the OK key to confirm your selection. The
flashing cursor under the parameter number indicates that the keypad is in parameter
mode.
•
Use the
↔
key to switch to edit mode. The flashing cursor disappears.
•
Using the
↑
or
↓
key, you can to select or set the correct parameter value.
•
Press the OK key to confirm the selection or setting.
•
Use the
↔
key to switch back to parameter mode again. The flashing cursor appears
again.
•
Use the
↑
key to choose the next parameter.
9.9.6
Manual operation
The inverter can be controlled using the DBG60B keypad in manual operation (Context
menu
→
Manual operation). The 7-segment display on the unit shows "H" during manual
operation.
The binary inputs will be without any functions for the duration of manual operation, with
the exception of a /Controller inhibit. A binary input "/Controller inhibit" must be assigned
a "1" signal to enable the drive to be started in manual operation.
The direction of rotation is not determined by the "CW/stop" or "CCW/stop" binary
inputs. Instead, you select the direction of rotation using the DBG60B keypad.
•
Enter the required speed and then the direction of rotation (+ = CW/– = CCW) using
the sign key (+/–).
Manual operation remains active when the power supply is switched off and on;
however, the inverter is then inhibited.
•
Use the "Run" key to enable and start the inverter at n
min
in the selected direction of
rotation. The speed is increased and decreased using the
↑
and
↓
keys.
NOTE
The signals at the binary inputs take effect as soon as manual operation is finished. A
binary input /Controller inhibit does not have to be switched from "1" to "0" and back to
"1". The drive can start according to the signals at the binary inputs and the setpoint
sources.
HAZARD!
Risk of crushing if the motor starts up unintentionally.
Severe or fatal injuries.
•
Ensure that the motor cannot start inadvertently, for example, by removing the
electronics terminal block X13.
•
Additional safety precautions must be taken depending on the application to avoid
injury to people and damage to machinery.