System Manual V2 – MOVITRAC® B
95
5
Explanation of the parameters
Parameters
126
AI2 characteristic curve x1
Setting range –100 % ...
0
... +100 % (–10 V ...
0
... +10 V)
127
AI2 characteristic curve y1
Setting range –100 % ...
0
... +100 % (–n
max
...
0
... +n
max
/
0
... I
max
)
128
AI2 characteristic curve x2
Setting range –100 % ... 0 ...
+100 %
(–10 V ... 0 ...
+10 V
)
129
AI2 characteristic curve y2
Setting range –100 % ... 0 ...
+100 %
(–n
max
... 0 ...
+n
max
/ 0 ...
I
max
)
The characteristic curve is described by the coordinates x1/y1 and x2/y2, with which the analog input is evaluated.
13_ / 14_
Speed ramps 1 / 2
The ramp times refer to a setpoint change of n = 3000 rpm. Ramps t11/t21 up and t11/t21 down are effective when the setpoint is
changed. The stop ramp t13/t23 is in effect when the enable is withdrawn by pressing the STOP/RESET key or via the terminals.
130 / 140
Ramp t11 / t21 up
Setting range 0 ...
2
... 2000 [s]; Acceleration ramp
131 / 141
Ramp t11 / t21 down
Setting range 0 ...
2
... 2000 [s]; Deceleration ramp
134 / 144
Ramp t12 / t22
up = down
Setting range 0 ...
10
... 2000 [s]
The following applies to this ramp: UP = DOWN and CW = CCW.
Ramps t12/t22 are activated by a binary input
(→
P601 ... P608), which is set to
the function "Ramp switchover".
135 / 145
S pattern t12 / t22
(In preparation)
Setting range:
0
/ 1 / 2 / 3 (0 = off, 1 = weak, 2 = medium, 3 = strong)
The 2nd ramp (t12/ t22) of parameter sets 1 and 2 can be rounded with 3
pattern grades to achieve a smoother acceleration of the drive.
Effect of the S pattern:
A started S pattern is interrupted by the stop ramp t13/t23 and a changeover to
ramp t11/t21. Revoking the setpoint or a stop via the input terminals causes the
started S curve to be completed. This means the drive can still accelerate in
spite of the withdrawal of the setpoint.
136 / 146
Stop ramp t13 / t23
up = down
Setting range 0 ...
2
... 20 [s]; stop ramp when switching to the NO ENABLE
operating status
No.
FBG
Name
Description
Normalized setpoint
–100 %
–10 V
+100 %
–100 %
+100 %
+10 V
Input
value
0 %
0 V
Factory setting
Example
1
2
1
2
U
E
t
Setpoint specification
Without S pattern
With S pattern
P
i
f
kVA
Hz
n
Summary of Contents for MOVITRAC MC07B0037-2A3-4-00
Page 250: ......