System Manual V2 – MOVITRAC® B
131
6
Mains and motor connection
Project Planning
6.10.5 Voltage drop
Select the cable cross-section of the motor cable so the
voltage drop is as small as
possible
. An excessively high voltage drop means that the full motor torque is not
achieved.
You can determine the expected voltage drop using the following tables. For shorter
cables, you can calculate the voltage drop by converting in proportion to the length.
Cable cross sec-
tion
Load with I [A] =
4
6
8
10
13
16
20
25
30
40
50
63
80
100
125
150
Copper
Voltage drop U [V] with length = 100 m (328 ft) and
ϑ
= 70 °C (158 °F)
1.5 mm
2
5.3
8
10.6
13.3
17.3
21.3
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
2.5 mm
2
3.2
4.8
6.4
8.1
10.4
12.8
16
1)
1)
1)
1)
1)
1)
1)
1)
1)
4 mm
2
1.9
2.8
3.8
4.7
6.5
8.0
10
12.5
1)
1)
1)
1)
1)
1)
1)
1)
6 mm
2
4.4
5.3
6.4
8.3
9.9
1)
1)
1)
1)
1)
1)
1)
10 mm
2
3.2
4.0
5.0
6.0
8.2
10.2
1)
1)
1)
1)
1)
16 mm
2
3.3
3.9
5.2
6.5
7.9
10.0
1)
1)
1)
25 mm
2
2.5
3.3
4.1
5.1
6.4
8.0
1)
1)
35 mm
2
2.9
3.6
4.6
5.7
7.2
8.6
50 mm
2
4.0
5.0
6.0
1) Loading not permitted, in accordance with VDE 0100 part 430
Cable cross sec-
tion
Load with I [A] =
4
6
8
10
13
16
20
25
30
40
50
63
80
100
125
150
Copper
Voltage drop U [V] with length = 100 m (328 ft) and
ϑ
= 70 °C (158 °F)
AWG16
7.0
10.5
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
AWG14
4.2
6.3
8.4
10.5
13.6
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
AWG12
2.6
3.9
5.2
6.4
8.4
10.3
12.9
1)
1)
1)
1)
1)
1)
1)
1)
1)
AWG10
5.6
6.9
8.7
10.8
13.0
1)
1)
1)
1)
1)
1)
1)
AWG8
4.5
5.6
7.0
8.4
11.2
1)
1)
1)
1)
1)
1)
AWG6
4.3
5.1
6.9
8.6
10.8
13.7
1)
1)
1)
AWG4
3.2
4.3
5.4
6.8
8.7
10.8
13.5
1)
AWG3
2.6
3.4
4.3
5.1
6.9
8.6
10.7
12.8
AWG2
3.4
4.2
5.4
6.8
8.5
10.2
AWG1
3.4
4.3
5.4
6.8
8.1
AWG1/0
2.6
3.4
4.3
5.4
6.8
AWG2/0
2.7
3.4
4.3
5.1
1) More than 3 % voltage drop in relation to V
mains
= AC 460 V.