System Manual V2 – MOVITRAC® B
99
5
Explanation of the parameters
Parameters
4__
Reference signals
The following reference values are used for recording and signaling certain operating states. All signals of parameter group 4__ can be
output via binary outputs.
The signals are valid if the inverter has signaled
ready
after switch-on and there is no fault.
40_
Speed reference signal
The inverter issues the signal "1" at P403 if the speed is less than or greater
than the set reference speed.
Speed reference message
400
Speed reference value
Setting range 0 ...
750
... 5000 [rpm]
401
Hysteresis
Setting range 0 ...
100
... 500 [rpm]
402
Delay time
Setting range 0 ...
1
... 9 [s]
403
Signal = "1" when
0 / n < n
ref
1 / n > n
ref
43_
Current reference signal
(in preparation)
Signal if the output current is greater or less than the reference value.
Current reference signal
430
Current reference value
Setting range 0 ...
100
... 150 % I
N
431
Hysteresis
Setting range 0 ...
5
... 30 % I
N
432
Delay time
Setting range 0 ...
1
... 9 s
433
Signal = "1" when
0 / I < I
ref
1 / I > I
ref
No.
FBG
Name
Description
I
ref
-I
ref
P431
P430
t
P432
1
1
0
0
t
t
P433: | I | < I
ref
P433: | I | > I
ref
I [% I ]
N
P
i
f
kVA
Hz
n