System Manual V2 – MOVITRAC® B
49
4
UWS11A interface adapter RS-232 / RS-485 for mounting rail
Technical Data
4.11
UWS11A interface adapter RS-232 / RS-485 for mounting rail
Part number
822 689 X
The FSC11B or FIO11B is required for connecting the UWS11A.
Ambient temperature
0 ... 40 °C (32 ... 104 °F)
Degree of protection
IP20
Description
The UWS11A option converts RS-232 signals, for example from the PC, into RS-485 signals. These RS-485
signals can then be routed to the RS-485 interface of the MOVITRAC
®
B.
The UWS11A option requires a DC 24 V voltage supply (I
max
= DC 100 mA).
RS-232 interface
The connection between UWS11A and PC is made using a commercially available serial interface cable
(shielded!).
RS-485 interface
You can use the RS485 interface of the UWS11A to network up to 32 MOVITRAC
®
B units for communica-
tion (max. total cable length 200 m (656 ft)). Do not connect external terminating resistors because dynamic
terminating resistors are already installed.
Permitted cable cross-section:
One core per terminal 0.20...2.5 mm
2
(AWG 24...12)
2 cores per terminal 0.20...1 mm
2
(AWG 24...17)
Dimension drawing
The UWS11A option is mounted on a mounting rail (EN 50022-35 × 7.5) in the control cabinet.
22.5 (0.886)
75 (3.0)
83 (3.3)
1
2
3
4
5
24V
RS+
RS-
1
2
3
4
5
X1:
RS-485
X2:
RS-232
UWS
68 (2.7)
5 (0.2)
P
i
f
kVA
Hz
n