130
System Manual V2 – MOVITRAC® B
6
Mains and motor connection
Project Planning
6.10.4 Motor cable length
The maximum motor cable length depends on:
•
Cable type
•
Voltage drop in the cable
•
Set PWM frequency.
•
Using an output filter
The limit values in the tables do not apply if you use and output filter. The motor cable
length is then solely limited by the voltage drop on the motor cable.
MOVITRAC
®
B 400 / 500 V
0370
0450
0550
0750
Size
4
5
Fuses F11/F12/F13
I
N
90 A
110 A
150 A
175 A
Supply system cable L1/L2/
L3
AWG4
AWG3
AWG1
AWG2/0
PE conductor
AWG8
AWG6
AWG6
AWG6
Motor cable U/V/W
AWG4 AWG3
AWG1
AWG2/0
Unit terminal cross section
of the power section
M10 bolt with nut
Max. AWG2/0 crimp cable lug
MOVITRAC
®
B
Permitted maximum motor cable length in m (ft)
Size
0XS / 0S / 0L
2S 0055
2S 0075 /
2 / 3 / 4 / 5
Voltage V
mains
3 AC 400 V
3 AC 230 V
1 AC 230 V
3 AC 500 V
3 AC 400 V (125 % I
N
)
3 AC 230 V
3 AC 400/500 V
Shielded cable
4 kHz
1)
8 kHz
12 kHz
16 kHz
1) Standard setting
100 (328)
70 (230)
50 (160)
40 (130)
50 (160)
35 (110)
25 (82)
25 (82)
300 (984)
250 (820)
200 (656)
150 (492)
400 (1310)
300 (984)
250 (820)
200 (656)
Unshielded
cable
4 kHz
1)
8 kHz
12 kHz
16 kHz
200 (656)
140 (459)
100 (328)
80 (2640
100 (328)
70 (230)
50 (160)
50 (160)
900 (2950)
750 (2460)
600 (1970)
450 (1480)
1200 (3937)
900 (2950)
750 (2460)
600 (1970)
NOTE
Do not use an earth-leakage circuit breaker with long motor cables. The leakage
currents caused by cable capacitance may cause mis-tripping.