24
System Manual V2 – MOVITRAC® B
4
Technical data of MOVITRAC® B
Technical Data
4.4.3
AC 400 / 500 V / 3-phase / size 0S / 0.55 ... 1.5 kW / 0.74 ... 2.0 HP
MOVITRAC
®
MC07B (3-phase supply system)
0005-5A3-4-
x0
0008-5A3-4-
x0
0011-5A3-4-
x0
0015-5A3-4-
x0
Part number, standard unit (-00)
Part number "Safe stop" (-S0)
1)
1) The MC07B...-S0 unit type must always be supplied with external voltage.
828 517 9
828 995 6
828 518 7
828 996 4
828 519 5
828 997 2
828 520 9
828 998 0
INPUT
Rated mains voltage
V
supply
3 × AC 380 ... 500 V
Rated mains frequency
f
supply
50 / 60 Hz ± 5%
Rated mains current, 100 % operation
Rated mains current, 125 % operation
I
supply
I
supply 125
AC 1.8 A
AC 2.3 A
AC 2.2 A
AC 2.6 A
AC 2.8 A
AC 3.5 A
AC 3.6 A
AC 4.5 A
OUTPUT
Output voltage
U
A
3 × 0 ... V
supply
Recommended motor power 100 % opera-
tion
Recommended motor power 125 % opera-
tion
P
Mot
P
Mot 125
0.55 kW /
0.74 HP
0.75 kW / 1.0
HP
0.75 kW / 1.0
HP
1.1 kW / 1.5
HP
1.1 kW /
1.5 HP
1.5 kW /
2.0 HP
1.5 kW /
2.0 HP
2.2 kW /
3.0 HP
Rated output current 100 % operation
Rated output current 125 % operation
I
N
I
N 125
AC 2.0 A
AC 2.5 A
AC 2.4 A
AC 3.0 A
AC 3.1 A
AC 3.9 A
AC 4.0 A
AC 5.0 A
Apparent output power 100 % operation
Apparent output power 125 % operation
S
N
S
N 125
1.4 kVA
1.7 kVA
1.7 kVA
2.1 kVA
2.1 kVA
2.7 kVA
2.8 kVA
3.5 kVA
Minimum permitted braking resistance value
(4 quadrant operation)
R
BW_min
68
GENERAL INFORMATION
Power loss 100 % operation
Power loss 125 % operation
P
V
P
V 125
40 W
45 W
45 W
50 W
50 W
60 W
60 W
75 W
Current limitation
150 % I
N
for at least 60 seconds
Terminal cross section / tightening torque
Terminals
4 mm
2
/ AWG12 / 0.5 Nm / 4 lb in
Dimensions
W × H ×
D
80 × 185 × 163.5 mm / 3.1 × 7.28 × 6.437 in
Weight
m
1.5 kg / 3.3 lb
80 (3.1)
163.5 (6.437)
185 (7.28)
196 (7.72)
285 (1
1.2)
70 (2.8)
159.5 (6.280)
149 (5.87)
6 (0.2)
6 (0.2)
220 (8.66)
P
i
f
kVA
Hz
n
Summary of Contents for MOVITRAC MC07B0037-2A3-4-00
Page 250: ......