DIAGNOSTICS
1.1
ALARM MANAGEMENT
The system integrates management of malfunctions and faults, signalled by specific alarms through:
HMI, directly on the system;
SMS, to the phone numbers connected to the system;
browser, with remote connection (via VPN protocol).
Alarm management is only possible:
directly from the HMI,
with remote connection, with “Seneca JMobile Client”
through the “Alarms” page
(Fig. 52 on page 65)
.
When an alarm is triggered, perform the following operations in the given order:
1.
access the “Alarms” page on the HMI;
18.
check the alarm;
19.
to solve the alarm, refer to
“1.1.1 Alarm list” on page 96
;
20.
reset the alarm.
1.1.1 Alarm list
Alarms are divided into 2 categories:
blocking alarms;
non-blocking alarms.
The following table shows the code, description, cause and solution of each blocking alarm.
Code
Alarm
Description
Cause
Solution
OT025
EMERGENCY (MUSHROOM)
An “EXTERNAL EMERGENCY
CONTROL” signal has been
configured among the config
-
urable digital inputs and the
contact connected to this input
is open.
- Check the correct configura
-
tion of the digital inputs in the
SETTINGS> IO DIGITAL TYPE
section of the HMI panel. -
Check the correct wiring of the
auxiliary contacts of the
“EXTERNAL EMERGENCY
CONTROL” signal, usually it is
an emergency button. Check
that the emergency button has
been released.