In case of a pressure increase PV > SP, or the dual case in which the pumps must be switched off
in sequence, the behaviour is the same as described in 1, 2, 3 but the pump switch-off conditions
are as follows:
- PV > SP;
- CO = 0%;
the start separation time
(62 -
Fig. 60 on page 74)
set in the “Pump parameters” screen in
“1.1.7.3 “Pump parameters” screen” on page 74
has elapsed.
The above behaviour is also applicable to flow control but not to level control.
1.2.2 System stop
To stop the system, cut off the supply to the system.