User Manual
DIGITAL INPUTS
No. 3 pumps, No. 2 floats, No. 1 level probe
1
+13 V
COMMON INPUTS IN1..5
2
IN1
PUMP 1 DIRECT CONTACTOR FEEDBACK
3
IN2
PUMP 1 CIRCUIT BREAKER
4
IN3
PUMP 1 START FLOAT
5
IN4
PUMP 2 DIRECT CONTACTOR FEEDBACK
6
IN5
PUMP 2 CIRCUIT BREAKER
7
+13 V
COMMON INPUTS IN6..10
8
IN6
PUMP 2 START FLOAT
9
IN7
PUMP 3 DIRECT CONTACTOR FEEDBACK/ CONFIGUR-
ABLE (*)
10
IN8
PUMP 3 CIRCUIT BREAKER/CONFIGURABLE (**)
11
IN9
PUMP 3 START FLOAT/cONFIGURABLE(**)
12
IN10
CONFIGURABLE
13
+13 V
COMMON INPUTS IN11..15
14
IN11
CONFIGURABLE
15
IN12
CONFIGURABLE
16
IN13
CONFIGURABLE
17
IN14
CONFIGURABLE
18
IN15
CONFIGURABLE
Tab. 40
RTU settings for Configurations 7 and 8: digital inputs
(*) If the configuration provides for 2 pumps “
IN7
” becomes PUMP STOP FLOAT
(**) If two pumps are configured , “
IN8
” and “
IN9
” become freely configurable
LIFTING
FILLING
or LSH3 “start Pump3”
or LSH2 “start Pump2”
or LSH1 “start Pump1”
or LSH0 (STOP)
or LSH0 (STOP)
or LSH1 “start Pump1”
or LSH2 “start Pump2”
or LSH3 “start Pump3”
LT (level probe