Doc. MI004620-I
S6001 Pump controller
Rev. 0
www.seneca.it
20 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
USB port
Host interface V2.0 max. 500 mA
Hardware clock
Clock/calendar with buffer battery
Time zone
Automatic
Clock precision
<100 ppm
Voltage
18-32 Vdc
Rated current (at 24 Vdc)
0.30 A
Tab. 19 HMI hardware characteristics
Radiated disturbance test
Class A
Electrostatic discharge immunity tests
8 kV (electrostatic discharge in air) EN 61000-4-2
4 kV (electrostatic discharge from contact)
Radiated radio frequency electromagnetic
immunity tests
80 MHz ÷ 1 GHz, 10 V/m
1.4 GHz ÷ 2 GHz, 3 V/m
2 GHz ÷ 2.7 GHz, 1 V/m
Tests of immunity to fast network transistors
± 2 kV dc power port EN 61000-4-4
± 1 kV signal line
Tests of immunity to power surges
± 0.5 kV dc power port (from ground to line)
± 0.5 kV dc power port (from line to line)
± 1 kV signal line (from line to ground)
Immunity to conducted interferences, in
-
duced by radiofrequency fields
0.15 ÷ 80 MHz, 10 V
Immunity tests to voltage dips, short inter
-
ruptions and voltage variations
Port: Network AC:
Level:
100% life: 1 cycle and 250 cycles (50Hz);
40% life: 10 cycles (50-Hz);
70% life: 25 cycles (50-Hz);
Phase: 0°-180°
Tab. 20 HMI electromagnetic compatibility