Doc. MI004620-I
S6001 Pump controller
Rev. 0
www.seneca.it
107 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
COM
Changing the system adjustment Set Point. The command works only if the type of system
application is pressure/flow. Il campo <valore del Set Point> deve contenere un numero; se è
necessario indicare un numero decimale si deve utilizzare il punto ‘.’ (per esempio “5,5” deve
essere inserito come “5.5”). If you enter a lower number at the beginning of the system ad
-
justment scale, the Set Point is set to the beginning of the scale. If you enter a number higher
than the end of the system adjustment scale, the Set Point is set to the end of the scale.
TX
SET SP <Set Point value>
RX
SET SP <Set Point value> <Set Point unit of measurement> OK
ES
Set the Set Point to 5.5
TX: SET SP 5.5
RX: SET SP 5.5 bar OK
If the end of scale is set to 10.0 bar and you try to set it to 11.0 bar, it is set to the end of scale
value of 10.0 bar.
TX: SET SP 11
RX: SET SP 10.0 bar OK
Tab. 79 SMS 3 command
COM
Requesting the system status. The system responds with a summarizing message containing
the current operation of the pump group, the Set Point, the adjustment value measured, the
number of non-blocking alarms (WARNINGS) and the number of blocking alarms (ALARMS).
TX
STATUS
RX
SET= <Set Point value> <Set Point unit of measurement>
PV=<process variable value> <process variable unit of measurement>
P1:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR>
P2<MAN/AUTO> <RUN/RUN_INV/STOP/ALR>
P3:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
P4:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
P5:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
P6:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
WARNING:<number of non-blocking alarms>
ALARMS:<numbers of blocking alarms>