DIGITAL INPUTS
No. 1 inverter, No. 3 pumps
1
+13 V
COMMON INPUTS IN1..5
2
IN1
PUMP 1 INVERTER CONTACTOR FEEDBACK
3
IN2
PUMP 1 DIRECT CONTACTOR FEEDBACK
4
IN3
PUMP 2 INVERTER CONTACTOR FEEDBACK
5
IN4
PUMP 2 DIRECT CONTACTOR FEEDBACK
6
IN5
PUMP 3 INVERTER CONTACTOR FEEDBACK
7
+13 V
COMMON INPUTS IN6..10
8
IN6
PUMP 3 DIRECT CONTACTOR FEEDBACK
9
IN7
INVERTER CIRCUIT BREAKER
10
IN8
PUMP 1 CIRCUIT BREAKER
11
IN9
PUMP 2 CIRCUIT BREAKER
12
IN10
PUMP 3 CIRCUIT BREAKER
13
+13 V
COMMON INPUTS IN11..15
14
IN11
INVERTER RUN FEEDBACK
15
IN12
CONFIGURABLE
16
IN13
CONFIGURABLE
17
IN14
CONFIGURABLE
18
IN15
CONFIGURABLE
Tab. 25