Doc. MI004620-I
S6001 Pump controller
Rev. 0
www.seneca.it
104 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
Code
Alarm
Description
Cause
Solution
OT053
PUMP 2 ABSORPTION (A) - H
OT054
PUMP 2 ABSORPTION (A) -
HH
OT055
PUMP 3 ABSORPTION (A) - LL
See CAUSE and SOLUTION
of ALARMS OT047, OT048,
OT049, OT050 for the “PUMP 3
ABSORPTION” signal
OT056
PUMP 3 ABSORPTION (A) - L
OT057
PUMP 3 ABSORPTION (A) - H
OT058
PUMP 3 ABSORPTION (A) -
HH
OT059
PUMP 4 ABSORPTION (A) - LL
See CAUSE and SOLUTION
of ALARMS OT047, OT048,
OT049, OT050 for the “PUMP 4
ABSORPTION” signal
OT060
PUMP 4 ABSORPTION (A) - L
OT061
PUMP 4 ABSORPTION (A) - H
OT062
PUMP 4 ABSORPTION (A) -
HH
OT063
INVERTER FREQUENCY AN-
ALOGUE PROBE FAULT (HZ)
An “INVERTER FREQUENCY
FEEDBACK” signal has been
configured among the config
-
urable analogue inputs, but the
probe is not connected or is not
working properly.
- Check the configuration of the
digital inputs in the SETTINGS
> IO ANALOGUE TYPE sec-
tion of the HMI panel is correct.
Check the wiring of the probe is
correct - Check the polarity of
the probe signal.
OT065
EXPANSION MODULE 1 COM-
MUNICATION ALARM
At least 4 pumps have been
configured, which requires
the installation of an expan
-
sion module for the P4 pump,
Z-D-IO type, connected to the
RS485 that does not respond to
MODBUS queries
- Check the RS485 data con
-
nection cable for correct con
-
nection and polarity of the A/B
signals between the pump
controller and the Z-D-IO ex
-
pansion module. Verify that the
parameters of the RS485 serial
set in the dip switches of the
Z-D-IO expansion module cor
-
respond to those configured in
the pump controller.