Alarm
Description
Cause
Solution
OT001
P1 M/A INCONSISTENCY
The pump controller is sending
the pump start command, but
the contactor status contact sig
-
nals the pump is switched off
- Check the wiring in the termi
-
nal box of the inputs/outputs re
-
lated to the feedback and pump
control. - Check that the pump
power supply contactor is work
-
ing correctly - Check that the
auxiliary contacts of the pump
supplying contactor are of the
normally open type with con
-
tactor coil resting - Check the
wiring of the auxiliary contacts
of the pump supply contactor is
correct
WARNING: The wiring de
-
pends on the type of system
(ref. S6001 System Type Lim
-
its_v1.5.xls).
OT002
P1 THERMAL SWITCH
The pump automatic circuit
breaker is switched off and the
pump is not powered
- Check the wiring in the ter
-
minal block for the status of
the pump automatic circuit
breaker. - Check that the aux
-
iliary contacts of the automatic
circuit breaker are normally
open. ATTENTION: The wiring
depends on the type of system
(ref. S6001 System Type Lim
-
its_v1.5.xls).
OT003
P1 ANOMALY
The inverter connected to the
pump is faulty
- If wired inverter: check the wir
-
ing of the fault signal from the
inverter is correct.
- If ModBUS inverter: check the
RS485 data connection cable
for correct connection and po
-
larity of the A/B signals. Check
whether any abnormal detec
-
tions have appeared in the local
inverter interface. Consult the
inverter supplier's manual.
OT005
P2 M/A INCONSISTENCY
See CAUSE and SOLUTION
of ALARMS OT001, OT002,
OT003
OT006
P2 THERMAL SWITCH