FULL FUNCTIONAL TEST
This procedure allows you to test the protective and control functions of the relay more fully
than the initial checkout procedure does.
Equipment Required
The following equipment is necessary to complete a full functional test:
1.
Communications terminal with EIA RS-232-C serial communication interface
2.
Data cable to connect terminal and relay
3.
Source of relay control power
4.
Source of synchronized three-phase voltages and at least two currents
5.
Ohmmeter or contact opening/closing sensing device
6.
Timer with contact inputs for start and stop
What Should Be Tested
A full functional test includes the initial checkout procedure and the additional steps described
below. In general, these tests assure that the relay settings match your application rather than
checking relay performance. For commissioning purposes, your company policy may require
you to perform the full functional test. For maintenance purposes, a quick test of selected
fault types and zones should suffice. For example, test a Zone 1 AG fault, Zone 2 BC fault,
and a Zone 3 ABC fault.
SETTING TEST
Purpose:
Ensure that the relay accepts settings.
Method:
1.
Gain Level 2 Access (see ACCESS and 2ACCESS commands in Section 3:
COMMUNICATIONS).
2.
Change one setting. For example, change the Zone 1 reach from 80%
to 82%.
Type
SET
and press
<ENTER>
several times.
Following the Z1% prompt, type
82
and press
<ENTER>.
3.
To complete the setting procedure, type
END
and press
<ENTER>.
Type
Y <ENTER>
at the prompt:
"
OK (Y or N)?
"
The relay com-
7-12
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 920508
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...