4.
System is attempting to transmit information, but cannot due to handshake line conflict.
Check communications cabling.
5.
System is in the XOFF state, halting communications. Type
<CTRL> Q
to put system
in XON state.
Tripping Output Relay Remains Closed Following Fault
1.
Output relay contacts burned closed.
2.
Main board failure.
No Prompting Message Issued to Terminal upon Power-Up
1.
Terminal not connected to system.
2.
Wrong baud rate.
3.
Terminal improperly connected to system.
4.
Other port designated AUTO in the relay settings.
5.
Port timeout interval set to a value other than zero.
System Does Not Respond to Faults
1.
Relay improperly set. Review your settings with the SHOWSET command.
2.
Improper test settings.
3.
PT or CT input cable wiring error.
4.
Check self test status with STATUS command.
5.
Check input voltages and currents with METER command and TRIGGER and EVENT
sequence.
Terminal Displays Meaningless Characters
1.
Baud rate set incorrectly. Check terminal configuration. See Section 3:
COMMUNICATIONS.
7-44
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 931227
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...