Table 7.1: Fault Locator Test Values
LOCATION
TYPE
VA
VB
V C
I A
IB
I C
UNITS
75 miles
A G
33.5
74.93
74.81
3.23
0 . 0 0
0.00
V or A
0.00
-129.2
129.2
-80.4
0 . 0 0
0.00
Degrees
B C
67.00
44.3244.32 0.00
4 . 7 7
4.77
V or A
0.00
-139.1
139.1
0.00
-170.1
9.9
Degrees
85 miles
AG
35.59
74.39
74.27
3.03
0.00
0.00
V or A
0.00
-128.6
128.7
-80.4
0.00
0.00
Degrees
B C
67.00
45.5245.52 0.00
4 . 4 7
4.47
V or A
0.
-137.4
137.4
0.00
-170.1
9.9
Degrees
135 miles
A G
4 3 . 0 7
72 .49
72 .39
2.31
0 . 0 0
0 . 0 0
V or A
0 . 0 0
-126.7
126.8
-80.4
0 . 0 0
0 . 0 0
Degrees
B C
67.00
5 0 . 1 4
5 0 . 1 4
0 . 0 0
3.4
3 . 4 0
V or A
0 . 0 0
-131.9
131.9
0 . 0 0
-170.1
9 . 9
Degrees
Faults at 75 miles are within Zone 1, since the Zone 1 reach setting is 80.0 % of the 100 mile
positive-sequence line impedance (see Z1 % in the settings). Faults at 85 miles are beyond
Zone 1, but within the 120 % setting of Zone 2 (see 22 % in the settings). Faults at 135 miles
are beyond Zones 1 and 2, but within Zone 3, set to 150 % (see Z3 % in the settings).
Faults listed in Table 7.1 cause certain combinations of output relays to close and front panel
LEDs to illuminate. Table 7.2 shows the results. Please remember to press the target reset
button between faults. Also note that these tests assume you are using a breaker simulator. If
you are not using a breaker simulator, remember to zero out the MTO logic mask.
Table 7.2: Output Contact and Target LED Results
LOCATION
TYPE
OUTPUT RELAYS
TARGET LED
75 mi
AG
TRIP, A3
G1
75 mi
BC
TRIP, A3
ø 1
85 mi
AG
TRIP, A3
G2
85 mi
BC
TRIP, A3
ø 2
135 mi
AG
TRIP, A4
G3
135 mi
BC
TRIP, A4
ø3
7-10
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 920508
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...