EXAMPLE EVENT REPORTS
Externally Triggered Event Report
The relay records an eleven cycle event report when you issue the TRIGGER command. This
command does not affect the protective functions of the relay. The event type listing EXT
signifies an externally triggered event. For events triggered by this command, the report does
not include a fault location, fault impedance in secondary ohms, fault duration, or maximum
fault current. Use the TRIGGER command to generate an event report for plotting voltage
and current phasors during normal load conditions prior to releasing the relay for service.
Example Event Report 1 shows the first cycle of normal operating conditions for Breaker 3 in
the system shown in Figure 4.1. The event report was generated with the TRIGGER
command. Note that the line breaker is closed, as signified by the 5 in the 52A column.
Event report data for the voltages and currents is displayed in rectangular format. You can
easily convert these rectangular values to polar format as described under Interpretation of
Voltage and Current Data. Section 6: INSTALLATION includes a blank form for plotting
voltage and current phasors. A completed SEL Direction and Polarity Check Form using the
first two rows of data from the event report follows Example Event Report 1.
Using the voltage and current phasor diagrams at the end of the SEL Direction and Polarity
Check Form, note that the current and voltage phase rotation is ABC in the clockwise
direction. This phase rotation must match the rotation of your system. In addition, note that
the load is flowing out from Breaker 3 as indicated by each phase current lagging the respec-
tive phase voltage by the load flow angle.
Date Code 920423
Event Reporting
SEL-221F, -1 Instruction Manual
4-9
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...