To change the password for Access Level 1 to Bike enter the following:
The relay responds by setting the password, pulsing closed the alarm relay, and transmitting
the response "Set."
After entering new passwords, type
PASSWORD <ENTER>
to inspect them. Make sure
they are what you intended and record the new passwords. There is no communications
procedure to access the relay without the passwords.
Passwords can be any length up to six numbers, letters, or any other printable characters
except delimiters (space, comma, semicolon, colon, slash). Upper and lower case letters are
treated as different characters. Examples of valid, distinct passwords include:
OTTER otter Ot3456 +TAIL+ !@#$%^ 123456 12345. 12345
If the passwords are lost or you wish to operate the relay without password protection, install
JMP103 on the main board. With no password protection, you may gain access without
knowing the passwords and view or change current passwords and settings.
SET
SET allows entry of relay settings. At the setting procedure prompts, enter new data or press
<ENTER>
to indicate no change.
The SET command prompts you for each setting. The relay checks new settings against
established limits twice. If the setting is within primary setting range, the relay prompts you
for the next setting. Press
<ENTER>
to retain an existing setting.
The first check is a primary setting limit check, the second is a secondary setting limit check.
The primary check is intended as a rough guideline for individual settings and ensures that
settings fall within a reasonable range. The secondary check compares the entire group of
settings against the individual secondary setting limits shown in Section 2: SPECIFICA-
TIONS.
Date Code 920508
Communications
SEL-221F, -1 Instruction Manual
3-21
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...