background image

  1 

I56-2798-002 

 

  

 7/2/2019

Specifications

Operating Voltage: 

18-35VDC, 18-35VAC, 115VAC, 230VAC

Operating  Current  (R-10TA/R14TA): 

23mA DC @ 24V, 59mA AC @ 24VAC; 150mA AC @ 120VAC, 180mA AC @ 240VAC

Operating  Current  (R-20TA/R-24TA): 

40mA DC @ 24V, 92mA AC @ 24VAC; 220 mA AC @ 120VAC, 260mA AC @ 240VAC

Operating Temperature: 

–40°F to 158°F (–40°C to 70°C)

Humidity Range: 

10% – 85% non-condensing

Dimensions: 

R-10TA/R-20TA: 3.5

×

 2.5

×

 1.25

D (89 mm H 

×

 64 mm W 

×

 32 mm D)

 

R-14TA/R-24TA: 3.5

×

 

10″

×

 1.25

D (89 mm H 

×

 254 mm W 

×

 32 mm D)

Accessories: 

R-10TA/R-20TA – 2 mounting screws; R-14TA/R-24TA – 4 mounting screws

Contact Ratings: 

24VDC 

7A

 

120VAC 10A

 120VAC 

1

/

6

 HP

 

230VAC 7A

Notice: 

This manual should be left with the owner/user of this equipment.

INSTALLATION AND MAINTENANCE INSTRUCTIONS

R-10TA/R-20TA/R-14TA/R-24TA 

Multi Voltage Relay

Models R-10TA/R-20TA and R-14TA/R-24TA are multi voltage 
relays with terminal strip field wiring connections, mounting 
track and hardware. The R-10TA is a single 1 FORM C (SPDT) 
relay with a red LED and the R-14TA is a 4-gang 1 FORM C 

(SPDT) relay with 4 red LEDs. The R-20TA is a single 2 Form C 
(DPDT) relay with a red LED and the R-24TA is a 4-gang 2 Form 
C (DPDT) relay with 4 red LEDs. The  LEDs indicate the energi-
zation of the Relay Coil.

C0567-01

NC

C

NO

18-35 V

115 V
230 V

Not used

0V

18-35 VDC, 18-35VAC, 115VAC, 230VAC

R-10TA/R14TA Relay

R-20TA/R24TA Relay

C0527-01

NC

C

NO

NC

C

NO

18-35 V

115 V
230 V

Not used

0V

18-35 VDC, 18-35VAC, 115VAC, 230VAC

Non-Power

Limited

Power

Limited

+

+

+

I56-2798-00

2

3333 Unity Drive, Mississauga, Ontario L5L 3S6

800/736-7672, Télécopieur : 905-812-0771

www.systemsensor.ca

General Description