putes internal settings and compares them against fixed limits. If all
settings are within acceptable ranges, the ALARM contact closes momen-
tarily as the new settings are enabled unless an alarm condition already
exists (e.g., self test failure).
4.
Use the SHOWSET command to inspect settings. Make sure your change
was accepted.
Type
SHOWSET
and press
<ENTER>.
5.
Use SET and SHOWSET again to restore the initial values and check the
settings.
6 . Type
LOG MTU
and press
<ENTER>.
7.
Change one bit in the MTU logic mask. For example, remove the Z3T bit
from the first row of the Relay Word as shown in the following example.
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-13