Alarm Contact Closed
1.
Power is off.
2.
Blown fuse.
3 .
Power supply failure.
4.
Improper EPROMs or EPROM failure.
5 .
Main board failure.
FIRMWARE UPGRADE INSTRUCTIONS
SEL may occasionally offer firmware upgrades to improve the performance of your relay.
These instructions explain how to install new firmware.
The modifications require that you power down the relay, remove its front panel, pull out the
drawout unit, exchange several integrated circuit chips, and reassemble the relay. If you do
not wish to perform the modifications yourself, we can assist you. Simply return the relay
and integrated circuit chips to us. We will install the new chips and return the unit to you
within a few days.
Warning:
This procedure requires that you handle electrostatic discharge sensitive com-
ponents. If your facility is not equipped to work with these components, we
recommend that you return the relay to SEL for firmware installation.
Upgrade Instructions
1.
If the relay is in service, disable its control functions. Turn off control power to the
relay.
2.
Remove the relay front panel by unscrewing the five front panel screws. With the front
panel removed, you can see the aluminum drawout chassis. The main board is attached
to the top of the drawout chassis. The power supply and transformer assembly are
attached to the bottom of the relay chassis.
3.
Disconnect the power supply and transformer secondary cables from the underside of the
drawout assembly.
7-46
Maintenance & Testing
SEL-221F, -1 Instruction Manual
Date Code 931227
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...