Example 3: Live-Bus/Dead-line Supervised Reclose
This example shows a successful live-bus/dead-line supervised reclosing sequence. Table 5.3
shows the recloser settings used for Example 3. Settings not shown in Table 5.3 are identical
to the example settings calculated earlier in this section. Figure 5.9 shows the timing of
Example 3. Settings marked N/A are not applicable to the example.
PSVC
S
27VLO
26.6
59VHI
106.2
25DV
N/A
SYNCP
A
25T
N/A
VCT
30
cycles
79OI
40
cycles
79RS
240
cycles
TDUR
9
cycles
Figure 5.9: Live Bus/Dead-Line Supervised Reclose
Referring to Figure 5.9 at t = 0, a permanent phase-ground fault occurs within the relay
Zone 1 reach. The relay detects the fault and asserts the TRIP outputs, fulfilling the first
requirement to initiate the reclosing sequence. Because the Z1G Zone 1 ground distance
element is set in the Mask for Reclose Initiate, reclosure is initiated.
Date Code 920508
Applications
SEL-221F, -1 Instruction Manual
5-39
Table 5.
4
: Recloser Settings for Example
3
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...