6.
For Z2DP settings exceeding approximately six cycles, the relay generates two
event reports: one for the Z3 element pickup, the other for TRIP output
assertion (and the Z2PT bit of the Relay Word).
7.
Calculate the Z2DP time delay using the difference from the Z3 element pickup
in the first event report to TRIP (and Z2PT bit) assertion in the second event
report.
REMOTE-END-JUST-OPENED TESTS
Purpose:
Method: 1.
2.
3.
4.
5.
6.
7.
8.
1.
Verify operation of relay REJO logic.
2.
Verify that elements set in the MPT logic mask are enabled to trip during a
REJO condition.
Check the relay settings and note the REJOE setting and pickup settings for the
50NG and 50P overcurrent elements.
Set the relay to trip upon assertion of the REJO bit by selecting only REJO in
the MTU logic mask.
If REJOE = P, apply balanced, three-phase current above the 50P setting. If
REJOE = G, apply balanced, three-phase current above the 50NG setting.
Remove current from two phases at the same time, leaving one current on. The
relay should trip when the REJO bit asserts and generate an event report.
Examine the event report to ensure that the REJO bit asserted for 1.5 cycles
approximately 0.5 cycles following dropout of the two phase currents.
Remove the REJO bit from the MTU logic mask.
Next, verify that the relay trips for assertion of elements set in the MPT mask
while the REJO bit is asserted. Deassert all the elements in the MTU, MTO,
and MTB logic masks. Set the Z3 bit in the MPT logic mask.
Apply balanced voltages to the relay. Apply balanced currents above the 50P
or 50NG overcurrent element settings (depending upon REJOE setting). Apply
a Zone 2 AG fault, with IB = IC = 0 A (Table 7.16 shows quantities for use
with the relay factory standard settings).
The relay should trip upon assertion of the REJO and Z3 bits. Examine the
relay event report to verify this.
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-35
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...