Figure 7.9a: Three-Phase Voltage and Two-Phase Current Source Test
Connections for Phase-Phase Mho Test
Figure 7.9b: Three-Phase Voltage and One-Phase Current Source Test
Connections for Phase-Phase Mho Test
3.
Determine the voltages and currents required to simulate a phase-phase fault at
the boundary of the desired relay reach (using ONEBUS or similar method).
Currents and voltages required to test the Zone 1 phase-phase element reach of
the example settings appear in Table 7.6:
Date Code 920508
Maintenance & Testing
SEL-221F, -1 Instruction Manual
7-23