The column headed DUR gives a measure of the fault duration. This is measured from the
first pickup of a Zone 1, 2, or 3, 51N, 67N or 50H relay element, until the first dropout of
all said relay elements. In other words, it is the duration of the first contiguous pickup of
relay elements found in the long event report, converted to units of cycles.
The CURR column shows the magnitude of the maximum phase-current measured at the
middle of the fault, in primary amperes. This information is useful for determining the row
pair used by the relay for fault location calculations.
IRIG
IRIG directs the relay to read the demodulated IRIG-B time code input at J201 on the rear
panel if a time code signal is input.
If the relay reads the time code successfully, it updates the internal clock/calendar time and
date to the time code reading and the relay transmits a message with relay ID string, date, and
time.
If no IRG-B signal is present or the code cannot be read successfully, the relay sends the
error message "IRIGB DATA ERROR."
Note:
Normally, it is not necessary to synchronize using this command because the relay
automatically synchronizes every few minutes. The command is provided to prevent
delays during testing and installation.
METER n
METER displays the phase-to-neutral and phase-to-phase voltages and currents in primary
kilovolts and amperes. METER also displays real and reactive power in megawatts and
megavars.
Date Code 920508
Communications
SEL-221F, -1 Instruction Manual
3-11
Summary of Contents for SEL-221F
Page 3: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 69: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 44 ...
Page 70: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 45 ...
Page 71: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 46 ...
Page 72: ...Date Code 920508 Specifications SEL 221F 1 Instruction Manual 2 47 ...
Page 110: ...Example Event Report 2 4 12 Event Reporting SEL 221F 1 Instruction Manual Date Code 930830 ...
Page 158: ...SETTINGS SHEET FOR SEL 221F RELAY PAGE 2 OF 6 DATE Date Code 921110 ...
Page 160: ...SETTINGS SHEET PAGE 4 OF 6 FOR SEL 221F RELAY DATE Date Code 930601 ...
Page 161: ...SETTINGS SHEET PAGE 5 OF 6 FOR SEL 221F RELAY DATE Date Code 961208 ...
Page 229: ...SEL 200 Series Relay Main Board Troubleshooting Test Points and Jumper Locations ...